sfondocorpo.jpg

Industrial products: ON-LINE MONITORS : - Chlorine dioxide (ClO2) :

 

Testomat® 2000 ClO2
 
 
 
Chlorine dioxide (ClO2
 
 
 
 
Testomat® 2000 ClO2
Testomat® 2000
 
On-line monitors for single sampling.  
 
it is an analyzer based on colour which controls and supervises chlorine dioxide in the water.
 
Every materials used for this analyzer have been produced to this purpose.
 
A piston pump carries out a  precise dosage.
 
The measuring chamber has been assembling inside of equipment and it has only two rings.
 
In this way there will not  be bacteria's growth and maintenance will be very easy.
 
The water and indicator consumption are reduced.It is perfect for utilities without control and /or maintenance  staff.
 
 *Accurate titration by piston-dosing pump

* Minimal reagent and water consumption    

* Two adjustable limit values with programmable switch functions     

* Analysis initiation: automatic time set intervals (0-99 minutes) or

   depending on the residual plant capacity  
 
* Monitoring of the filter capacity quantity-dependent (water meter) external control  

Programmable supplementary  program (for example to control a cooler or for  

   an analysis message)

*Monitoring of an analysis run and error messages, for example low water-pressure
 
 
-       titrometic analysis
 
-      dosage by piston pump
 
-      display of result in different units.

-      programmable two high values which work in exit (high value 1over passed,

       high value 2 over passed)

-      programmable analysis range between 0 – 99 minutes

-      possibility of volumetric analysis

-      6 release output : hardness value  above the first programmable value,

       hardness value above the second programmable value, washing,

       unworking alarm, maintenance request e AUX to head a cooler.

-      4 input: stop analysis, start analyisis, IN 1 zero-setting of water meter

       e IN 2 for a water meter

-      documentation of analysis mistakes

-      programmable supplementary program (for example: to start a cooler)

-      address of programmable supporter

-      galvanic division  between voltage high side and low side

-      within pressure regulator 0,1 – 8 bar

Accessories: output 0 (4) – 20mA, 0/2 - 10V or output RS232
 
                                                                              
 
Technical data:
Power supply:   230V, 115V or 24V 50-60Hz
Power consumption:  max. 30VA
Degree of protection: IP 65
Protection class:  I
Environment temperature: 10 - 45°C
Water temperature:  10 - 40°C
Operating pressure 0,1 – 8 bar (104 – 8 x 105 Pa)
Dimensions:  380 x 480 x 280mm (widthxheightxdepth.)
Instructions: english, french, german
Display:

italian, french, english, german (indicate on order)

Weight: approx 10,5 kg
                                              
 
 
Code numbers:
Code. Nr.
Testomat® 2000 ClO2
230V 50-60Hz, 0,1 – 8 bar
115V 50-60Hz, 0,1 – 8 bar
24V 50-60Hz, 0,1 – 8 bar
200340
200341
200342
Accessories:
output 0 (4) – 20mA
output RS 232
output 0/2 – 10 V
SD card
cleaning set for road delivery
cleaning set for air delivery
200300
200309
200308
200307
200012
200012S
 
 
Indicators for Testomat 2000 ClO2:
 
Type
mg/l
Code.Nr.
Set chlorine dioxide indicators 0 - 4,7 200798
 
 
We reserve every technical change.
www.apura.it Version11/2015
 
  www.apura.it     Version 2015
 
 

 

Apura s.r.l. – Piazza Porto, 3 – 25084 Gargnano (BS) – Italy
Tel. **39 / 031-4154820 – Fax **39 / 0365-1892024 – Ufficio Vendite/Sales office: **39 / 329-7915851 – Ufficio Tecnico/Technical department: **39 / 333-7388380 info@apura.it – P.IVA/VAT No.: IT03560460176